Use of IEEE 1588–2008 for a sampled value process bus in transmission substations
![Use of IEEE 1588-2008 for a Sampled Value Process Bus in Transmission Substations [I2MTC 2011].pdf Use of IEEE 1588-2008 for a Sampled Value Process Bus in Transmission Substations [I2MTC 2011].pdf](https://eprints.ingram.id.au/files/fullsize/918ce4a83b89baeedbe4cf2858f93992.jpg)
- Title
- Use of IEEE 1588–2008 for a sampled value process bus in transmission substations
- Subject
- IEC 61850
- IEC standards
- IEEE 1588
- performance evaluation
- protective relaying
- Synchronization
- Clocks
- smart grids
- Global Positioning System
- Substations
- time measurement
- power transmission
- Jitter
- power system simulation
- ethernet networks
- Oscillators
- Creator
- David M. E. Ingram
- Duncan A. Campbell
- Pascal Schaub
- Source
- 2011 IEEE International Instrumentation and Measurement Technology Conference, pp. 1-6
- Publisher
- IEEE
- Date
- 2011-05-10
- Relation
- ISBN 1091-5281
- Format
- application/pdf
- Language
- en
- Type
- Peer-reviewed Article
- info:eu-repo/semantics/conferencePaper
- info:eu-repo/semantics/acceptedVersion
- Identifier
- 10.1109/IMTC.2011.5944081
- Coverage
- Hangzhou, China
- Abstract
- IEC Technical Committee 57 (TC57) published a series of standards and technical reports for “Communication networks and systems for power utility automation” as the IEC 61850 series. Sampled value (SV) process buses allow for the removal of potentially lethal voltages and damaging currents inside substation control rooms and marshalling kiosks, reduce the amount of cabling required in substations, and facilitate the adoption of non-conventional instrument transformers. IEC 61850-9-2 provides an inter-operable solution to support multi-vendor process bus solutions. A time synchronisation system is required for a SV process bus, however the details are not defined in IEC 61850-9-2. IEEE Std 1588-2008, Precision Time Protocol version 2 (PTPv2), provides the greatest accuracy of network based time transfer systems, with timing errors of less than 100 ns achievable. PTPv2 is proposed by the IEC Smart Grid Strategy Group to synchronise IEC 61850 based substation automation systems. IEC 61850-9-2, PTPv2 and Ethernet are three complementary protocols that together define the future of sampled value digital process connections in substations. The suitability of PTPv2 for use with SV is evaluated, with preliminary results indicating that steady state performance is acceptable (jitter <
- 300 ns), and that extremely stable grandmaster oscillators are required to ensure SV timing requirements are met when recovering from loss of external synchronisation (such as GPS).
Collection
Citation
David M. E. Ingram, Duncan A. Campbell and Pascal Schaub, Use of IEEE 1588–2008 for a sampled value process bus in transmission substations, IEEE, 2011, accessed March 21, 2025, https://eprints.ingram.id.au/items/show/43
Position: 25 (25 views)